The complaint is almost always the same: one room is too warm, the last one
never gets there. The cause is rarely the boiler.
What the symptom tells you
When a manifold feeds several loops of different lengths, water does not
distribute itself fairly. It takes the easiest route. The shortest loop, with
the least resistance, receives more flow than it needs; the longest loop, with
the most, receives less. The result is a floor that heats unevenly — not because
the pipe is wrong or the heat source is undersized, but because nothing has been
done to equalise resistance across the circuits.
Balancing is that equalisation. It is not a repair. It is part of
commissioning.
Resistance is the currency
Every loop carries a resistance set by its length, its diameter, its bends
and the fittings on it. Water divides between parallel loops in inverse
proportion to those resistances. Without intervention, a sixty-metre loop and a
hundred-metre loop on the same manifold will not see the same flow, and the
shorter one will always win.
Balancing adds deliberate, adjustable resistance to the short circuits so
that every loop ends up with the flow the design intended. The valve on each
loop is not there to shut a circuit off. It is there to make an unequal system
behave as though it were equal.
What a flow meter does and does not tell you
A manifold fitted with flow meters shows, at a glance, what each loop is
receiving. That is diagnostic value, not a solution: the meter tells you a loop
is short of flow, not why.
Three different faults look identical on a flow meter:
the loop is genuinely unbalanced;
air is trapped in the loop;
the loop is partly blocked, or was kinked during installation.
Only the first is corrected by adjusting a valve. Opening up a blocked loop
raises the reading briefly and changes nothing about the floor temperature.
The order of operations
Balancing done in the wrong sequence is wasted work.
Flush the system first. Installation debris migrates to valves and meters.
Balancing a dirty system means balancing something that will change again within
a week.
Remove the air. Vent every manifold and every high point. Air compresses,
and it makes flow readings meaningless.
Confirm the pump delivers design head. If the pump is short, no valve
adjustment creates flow that is not there.
Open all loop valves fully, then measure. Establish the baseline before
changing anything.
Start with the index circuit — the loop with the highest resistance,
usually the longest. Leave it fully open.
Throttle the rest toward it. Bring every remaining loop down to its design
flow, working from the next most resistant to the least.
Re-check once the system reaches temperature. Readings shift as the system
stabilises.
Proportional balancing, in one sentence
Set the circuit that is hardest to feed, then bring every other circuit
into proportion with it — instead of adjusting each loop in isolation against a
number on a sheet.
Mistakes that undo the work
Balancing by feel. A hand on the floor is not a flow measurement.
Closing loops instead of throttling them. A closed loop is not a balanced
loop; it is an uncontrolled one.
Balancing before flushing. See step one.
Ignoring the mixing valve. In low-temperature underfloor systems the mixing
unit sets the supply temperature. Balancing flow while the supply temperature
drifts produces readings that mean nothing.
Leaving it undocumented. Balancing is a commissioning task with a record,
not an adjustment someone makes once and forgets.
When balancing will not fix it
If a loop stays cold after correct balancing, the cause is elsewhere:
Pipe undersized for the load, where the design never allowed enough flow in
the first place.
A kink — invisible under the screed, and the most common installation
defect in flexible pipe systems.
A blocked or air-locked loop, which reads as high resistance whatever the
valve position.
A pump at the end of its curve, delivering head that the index circuit
consumes entirely.
In these cases the remedy is in the pipe or the pump, not at the
manifold.
A commissioning record worth keeping
Loop lengths as installed, not as designed.
Design flow per loop.
Measured flow per loop after balancing.
Supply and return temperature at the manifold.
Pump setting.
Date, and who signed it off.
That record is what turns a complaint into a diagnosis two winters
later.
Where the components come in
A manifold with flow meters makes balancing possible. Pipe that resists
kinking makes it necessary less often. RITABLE's underfloor heating range covers
manifolds and accessories, and the PE-Xa pipe with an EVOH oxygen barrier is
specified for closed-loop heating where oxygen ingress has to be controlled.
If a circuit will not balance, the cause is usually found before the
manifold. Send us the loop schedule and your measurements and we will review the
circuit design against the pipe and manifold specification.