The manifold is where most underfloor heating mistakes begin
Pipe gets all the attention. The manifold is what decides whether the
system actually works as designed — and the first decision on it is the outlet
count.
What the manifold actually does
RITABLE's manifold documentation identifies four functions, and a system
that is missing any one of them runs effectively open-loop — it heats, but it
cannot be tuned:
Distribution — splits flow from the heat source (boiler or heat pump) to
the various zones or loops.
Control — valves or actuators regulate flow to each zone, enabling
individual room temperature control and zoning.
Balancing — flow meters or flow regulators equalise flow between zones, so
each area receives the heat it needs. This is what makes comfort and energy
efficiency possible at the same time.
Monitoring — temperature gauges or sensors show the water temperature
entering and leaving each zone, which is the first thing to look at when
troubleshooting.
One outlet = one loop
Outlet count is not chosen from the size of the building. It follows the
loop count — and loop count follows heat demand, floor area and pipe
spacing.
Four things drive it:
Heat demand per room. A room with high losses — large glazing, exposed
external walls — needs more pipe per square metre than an internal room of the
same area.
Pipe spacing. Tighter spacing means more pipe, which means shorter loops
for the same floor area.
Practical loop length. Very long loops raise pressure drop, demand more
pump head, and heat unevenly because the water has already given up heat by the
time it reaches the return. Keeping loops comparable in length is what makes
balancing possible at all.
Zoning requirement. Any room that must be controlled independently needs
its own loop — and therefore its own outlet.
The working rule: one manifold outlet per loop, plus spare capacity if
there is any realistic prospect of extending the system later.
The RITABLE manifold range

Brass manifolds JA-B1 and JA-B2 are available in 1/2", 3/4" and 1"
connection sizes.
For floors requiring more than eight loops, the standard approach is
multiple manifolds — each positioned to keep pipe runs short — rather than one
oversized unit. A single large manifold forces long pipe runs to the far corner
of the building, which is exactly the pressure-drop problem the loop limit
exists to avoid.
Do not forget the components around it
From the same product range:
Brass air vent — 1/2", 3/4". Trapped air is the single most common reason
one loop stays cold while the rest of the floor heats.
Brass ball valve — 1". Lets you isolate the manifold for servicing without
draining the whole system.
Brass adaptor — 1". Correct transition between manifold and distribution
pipework.
Bend support — protects the pipe at tight changes of direction, where the
wall is thinnest.
Floor heating module — for structured, repeatable installation.
A sizing checklist
How many rooms or zones need independent control?
Heat demand per room → pipe spacing → loop length.
Are loop lengths comparable enough that balancing will actually work?
Total loop count = manifold outlet count.
Add spare outlets where future extension is realistic.
Confirm the manifold connection size matches your pipework and
adaptors.
Budget the air vent, isolation valve and bend supports from the start — not
as an afterthought.
Conclusion
Get the loop count right and the manifold selection almost makes itself.
Get it wrong, and no amount of balancing at the manifold will fix a system where
the loops were never comparable to begin with.
View the manifold range — or tell our engineers the zone layout and we will
help you size it.